AC Enclosed Disconnect Switch PE69-30100

Model Number: PE69-30100
Stock status: Contact Us
Lead Time: Contact Us

Our Price: $249.00

Product Description

Enclosed AC Disconnect Switch, NEMA 4X (IP65), 100A 600VAC 3 Pole, Yellow Body With Red Rotary , UL508 approved.

Type: AC Disconnect
Phase/Poles: 3
Amps: 100
Material: Plastic
Warranty: 1 Year

    Technical Specifications                                                                                                        Technical Datasheet

Data according to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1

Type

 

..69..20

..69..25

..69..32

..69..40

..69..63

..69..80

..69..100

..69..125

Main Contacts

 

 

 

 

 

 

 

 

Rated thermal current Ith open

A

20

25

32

40

63

80

100

125

Rated thermal current Ith enclosed

A

20

25

32

40

63

80

100

110

Rated insulation voltage Ui 1)

V

690

690

690

690

690

690

1000

1000

Rated operational current Ie AC21A

A

20

25

32

40

63

80

100

125

Making capacity Ieff

3x380-440V

A

160

190

220

300

370

440

725

850

Breaking capacity

3x220-240V

A

160

180

200

250

330

380

580

680

 

3x380-440V

A

160

180

200

250

330

380

580

680

 

3x660-690V

A

80

110

140

170

190

220

330

420

Disconnection property performed up to

V

690

690

690

690

690

690

1000

1000

Motor switch               AC3

3x400V

A

12

16

23

30

37

37

60

72

Motor switch               AC3

3x220-240V

kW

3

4

5.5

7.5

11

11

18.5

22

Direct switching of single motors

3x380-440V

kW

5.5

7.5

11

15

18.5

18.5

30

37

 

 

3x660-690V

kW

5.5

7.5

11

15

18.5

18.5

22

30

Main switch

AC23

3x400V

A

16

20

25

32

45

45

72

85

Motor switch

AC23A

3x220-240V

kW

4

5.5

7.5

9

15

15

22

30

Main switch

AC23B

3x380-440V

kW

7.5

10

12.5

16

22

22

37

45

Safety switch

 

3x660-690V

kW

5.5

7.5

11

15

18.5

18.5

30

37

Rated conditional short-circuit current

kAeff

10

10

10

10

10

10

10

5

Max. fuse size                                        gL (gG)

A

25

35

40

40

63

80

100

125

Mechanical life

x103

200

200

200

200

100

100

100

100

Rated short-time wihstand current (1 sec. current)

A

250

300

400

500

600

850

1200

1500

Power loss per pole AC21 = Ith

 

 

 

 

 

 

 

 

 

P/pole [W]

 

PM, SH

0.322

0.503

0.824

1.288

2.739

4.416

5.330

8.328

 

 

LB, DM, PE

0.364

0.569

0.933

1.458

2.739

4.416

5.330

8.328

R/pole [mΩ]

 

PM, SH

0.805

0.805

0.805

0.805

0.690

0.690

0.533

0.533

 

 

LB, DM, PE

0.911

0.911

0.911

0.911

0.690

0.690

0.533

0.533

Cable cross sections

 

mm2

 

0.5 - 10

 

1 -

 25

4 -

 50

solid or stranded

 

AWG

 

20 - 8 (10)

 

16 -

3 (10)

10 - 0

0 (10)

flexible

 

mm2

 

0.5 - 6

 

4 -

 16

10

 35

 

 

AWG

 

20 - 10

 

16

 - 6

8

 2

flexible (+ multicore cable end)

 

mm2

 

0.5 - 6

 

0.75

 - 16

6 -

 35

 

 

AWG

 

20 - 10

 

16

 - 6

8

 2

Size of terminal screw

 

 

 

M3.5

 

 

M5

 

M6

Tightening torque

 

Nm

 

1.7 - 2.3

 

2.8

 - 4

1.7

- 4.5

Auxiliary contacts

 

 

 

 

 

 

 

 

 

Rated insulation voltage Ui 1)

 

V

 

 

6

90

 

 

 

Rated thermal current Ith, ithe

 

A

 

 

1

0

 

 

 

Switching capacity       AC15

220-240V

A

 

 

2

.5

 

 

 

AC15

380-440V

A

 

 

1

.5

 

 

 

Rated conditional short-circuit current

 

kAeff

 

 

3

 

 

 

 

Max. short circuit protection

gL (gG)

A

 

 

1

0

 

 

 

Cable cross sections

 

mm2

 

 

0.75

 - 2.5

 

 

 

Solid or stranded

 

AWG

 

 

14

 12

 

 

 

Flexible (+ multicore cable end)

 

mm2

 

 

0.75 -

2.5 (1.5)

 

 

 

 

 

AWG

 

 

18

 14

 

 

 

Data according to UL and cUL

 

 

 

 

 

 

 

 

 

Rated voltage

 

V

600

600

600

600

600

600

600

600

Ampere rating “General Use”

 

A

20

25

32

40

63

80

100

125

DOL rating 3-phase

110 - 120V

HP

1

1.5

2

2

3

5

10

15

 

220 - 240V

HP

3

5

5

5

10

10

25

30

 

440 - 480V

HP

7.5

10

10

10

20

20

50

60

 

550 - 600V

HP

10

10

15

15

25

25

60

60

DOL rating 1-phase

110 - 120V

HP

1

1

1

1

2

2

5

7.5

 

200 - 208V

HP

1

2

2

2

3

3

10

10

 

220 - 240V

HP

2

2

3

3

5

5

15

15

Fuse size (RK5)           Manual motor controller

A

40

50

50

70

90

110

125

125

5kA / 600V                  Motor disconnect

A

40

50

50

50

70

70

125

125

Tightening torque

Nm

 

1.7 - 2.3

 

2.8 - 4

1.7 - 4.5

 

lb.inch

 

11 - 20

 

24 - 35

15 - 40

1) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 6kV. Data for other conditions on request 2) The values after the slash are valid for switches 6-pole or more

  1. Suitable for no load application (A20A) above 690V
  2. Fuse RK1 / 10kA / 600V
  3. Uimp = 8kV

We're sorry. There are no products to list in this category.